![DAB PUMPS PWM 201 Instruction For Installation And Maintenance Download Page 96](http://html1.mh-extra.com/html/dab-pumps/pwm-201/pwm-201_instruction-for-installation-and-maintenance_495533096.webp)
ENGLISH
94
5.1.7
Setting other parameters
After the initial start-up procedure, the other pre-set parameters can be modified as required, by accessing the relative menus
and following the instructions for the specific parameters (see chapter 6). The most common parameters are: restart pressure,
regulation gain values GI and GP, minimum frequency FL, water failure time TB, etc.
5.2
Troubleshooting on initial installation
Fault
Possible causes
Remedy
The display shows
EC
Pump current (RC) not set
Set parameter RC (see section 6.5.1).
The display shows
BL
1) No water.
2) Pump not primed.
3) Flow sensor disconnected.
4) Entry of setpoint too high for pump.
5) Inverted direction of rotation.
6) Incorrect setting of pump current RC(*).
7) Maximum frequency too low (*).
8) SO parameter not set
correctly
9) MP minimum pressure parameter
not set correctly
1-2) Prime the pump ad ensure that there is no air in the pipelines. Check that intake or any
filters are not obstructed Check that the pipeline from the pump to the inverter is not
damaged or leaking.
3) Check the connections to the flow sensor.
4) Lower the setpoint or use a pump suited to system requirements.
5) Check the direction of rotation (see 6.5.2).
6) Set a correct value for pump current RC(*) (see 6.5.1).
7) If possible, increase FS or lower RC(*) (see 6.6.6).
8) set SO value correctly (see para. 6.5.14)
9) set MP value correctly (see para. 6.5.15
The display shows
BPx
1) Pressure sensor disconnected.
2) Pressure sensor faulty.
1) Check the pressure sensor cable connection.
BP1 refers to the sensor connected to Press 1, BP2 to press2,
BP3 to current sensor connected to J5
2) Replace the pressure sensor.
The display shows
OF
1) Excessive absorption.
2) Pump blocked.
3) Pump absorbs high current on start-up.
1) Check type of connection; star or delta. Check that the motor does not absorb current
over the max. admissible value for inverter. Check that the motor has all phases connected.
2) Check that the impeller or motor is not blocked or obstructed by foreign bodies. Check
motor phase connections
3) Reduce the acceleration parameter AC (see 6.6.11).
The display shows
OC
1) Incorrect pump current setting (RC).
2) Excessive absorption.
3) Pump blocked.
4) Inverted direction of rotation.
1) Set RC with the current according to the type of connection (star or delta) as stated on the
motor dataplate (see 6.5.1)
2) Check that the motor has all phases connected.
3) Check that the impeller or motor is not blocked or obstructed by foreign bodies.
4) Check the direction of rotation (see 6.5.2).
The display shows
LP
1) Low power supply voltage
2) Excessive voltage drop on line
1) Ensure presence of correct line voltage.
2) Check the power cable section
(see section 2.2.1).
Regulation pressure
greater than SP
FL setting too high
Reduce minimum operating frequency FL (if electric pump enables this)
The display shows
SC
Short circuit between phases
Ensure that the motor is in the correct condition and check connections to the latter
The pump never stops
1) Minimum flow threshold FT setting too low.
2) Short observation time(*).
3) Unstable pressure regulation(*).
4) Incompatible use (*).
1) Set a higher FT threshold
2) Set a higher FZ threshold
3) Wait for the self-learning process (*) or run quick learning mode (see para 6.5.9.1.1)
3) Correct GI and GP(*) (see 6.6.4 and 6.6.5)
4) Ensure that the system meets the operating requirements without the flow sensor (*) (see
section 6.5.9.1). Attempt to reset by pressing MODE SET + - to recalculate conditions
without the flow sensor.
The pump stops even
when not required
1)Short observation time(*).
2) Minimum frequency FL setting too high (*).
3) Excessively high setting of minimum
shutdown frequency FZ (*).
1) Wait for the self-learning process (*) or run quick learning mode (see para 6.5.9.1.1).
2) If possible set a lower FL value(*).
3) Enter a lower threshold for FZ.
The multi inverter
system does not start
One or more inverters have an incorrect RC
current setting.
Check the RC current setting on each inverter.
The display shows:
Press + to align this
config
One or more inverters have sensitive
parameters not aligned
Press + on the inverter that has the most recent and correct configuration of parameters.
In a multiple inverter
system the parametres
are not propagatable
1) Different passwords
2) Presence of non-propagatable
configurations
1) access each inverter individually and enter the same password on all, or remove the
password. See para. 6.6.16
2) modify the configuration so that it is propagatable; it is not admitted to propagate
configurations with FI=0 or FZ=0. See paragraph 4.2.2.2
(*) The asterisk refers to cases of systems without the flow sensor
Table 14: Troubleshooting
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...