If FZ is too low, the electropump might never stop even in the absence of flow, or with very low flows. This situation could
lead to damage of the electropump due to overheating.
Since the zero flow frequency FZ may vary as the Setpoint varies, it is important that
:
.
1.
Whenever the Setpoint is changed you check that the set value of FZ is adequate for the new Setpoint.
The auxiliary set points are disabled if the flow sensor is not used (FI=0) and when FZ is used in minimum frequency
mode (FZ ≠ 0)
.
CAUTION: the minimum frequency mode is the only operating mode without flow sensor admitted for multiple inverter systems.
Self-adaptive mode: this mode consists of a particular and efficient self-adaptive algorithm which allows operation in nearly all cases
without any problem. The algorithm acquires information and updates the relative parameters during operation.
To ensure optimal
operation, there should not be any substantial periodic variations on the hydraulic system, which cause significant differences
between values (such as solenoid valves that exchange hydraulic sectors with very different characteristics), as the algorithm adapts
only to one of these and cannot provide the expected results as soon as switching is performed. On the other hand, if the system
remains with similar characteristics (elasticity length and minimum required flow rate) there are no problems.
On each restart or reset of the unit, the self-learnt values are reset, and therefore a specific time interval is required to self-adapt.
The algorithm used, measures the various sensitive parameters and analyses the unit status to detect the presence and entity of the
flow. For this reason, and to avoid false errors, correct parameter settings are fundamental, and in particular:
•
Ensure that there are no system oscillations during regulation (if this occurs, adjust parameters GP and GI section 6.6.4
and
6.6.5)
•
Enter the correct rated current setting RC
•
Set an adequate minimum flow FT
•
Set the correct minimum frequency FL
•
Set the correct direction of rotation
WARNING: the self-adaptive mode is not allowed on multi-inverter systems.
IMPORTANT: In both operating modes the system is able to detect the lack of water by measuring the current absorbed by the pump
and comparing it with the parameter RC (see 6.5.1). If the maximum operating frequency FS is set with a value that does not enable
absorption of a value close to the current under full load of the pump, false water failure errors (BL) may occur. In this case, remedy
the situation as follows: turn on the utilities to reach the frequency FS and at this value, check pump absorption (easily seen on
phase current parameter C1 in the User menu), then set the current value reading on RC.
6.5.9.1.1
Fast self-learning method for auto-adaptive mode
The self-learning algorithm is adaptable to various systems automatically on acquisition of information on the type of system.
The system set-up process can be shortened by using the quick learning the procedure:
1)
Turn on the unit or, if already powered, press MODE SET + - simultaneously for 2 seconds to generate a reset.
2)
Enter the Installer menu (MODE SET -) set FI to 0 (no flow sensor) then in the same menu go to item FT.
3)
Turn on a utility and run the pump.
4)
Slowly turn off the utility to reach minimum flow (utility closed) and when this value stabilises, note the corresponding
frequency.
5)
Wait 1-2 minutes for the simulated flow reading; this is confirmed by shutdown of the motor.
6)
Turn on a utility to achieve a frequency that is 2 – 5 [Hz] greater than the previous frequency reading, and then wait
1-2 minutes for another shutdown.
IMPORTANT: the method is only effective if, while gradually closing the utility in point 4) the frequency remains at a fixed
value through to reading of the flow VF. It should not be considered a valid procedure if, after closure, frequency reaches
0 [Hz]; in this case the operations from point 3 must be repeated; otherwise leave the unit to self-learn for the time interval
specified above.
6.5.9.2
Operation with specific pre-defined flow sensor
This applies both to single and multiple sensors.
Use of the flow sensor enables effective measurement of the flow and the possibility of operation in special applications.
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...