![DAB PUMPS PWM 201 Instruction For Installation And Maintenance Download Page 106](http://html1.mh-extra.com/html/dab-pumps/pwm-201/pwm-201_instruction-for-installation-and-maintenance_495533106.webp)
ENGLISH
104
Table of correspondence of diameters and k-factors for flow sensor F3.00
Pipe diameter [inch]
Internal DN pipe
diameter [mm]
K-factor
Minimum flow l/min
Maximum flow
l/min
1/2
15
225,0
1,6
85
3/4
20
142,0
2,8
151
1
25
90,0
4,4
236
1 1/4
32
60,7
7,2
386
1 1/2
40
42,5
11,3
603
2
50
24,4
17,7
942
2 1/2
65
15,8
29,8
1592
3
80
11,0
45,2
2412
3 1/2
90
8,0
57,2
3052
4
100
6,1
70,7
3768
5
125
4,0
110,4
5888
6
150
2,60
159,0
8478
8
200
1,45
282,6
15072
10
250
0,89
441,6
23550
12
300
0,60
635,9
33912
14
350
0,43
865,5
46158
16
400
0,32
1130,4
60288
18
450
0,25
1430,7
76302
20
500
0,20
1766,3
94200
24
600
0,14
2543,4
135648
Table 20: Diameter of pipelines, FK conversion factor, minimum and maximum admissible flow
CAUTION: always refer to the manufacturer’s installation notes and compatibility of electric parameters of the flow sensor and those
of the inverter, as well as exact correspondence of connections. Incorrect settings will cause false flow readings with possible
undesired shutdown or continuous operation without stops.
6.5.12
FZ: Setting zero flow frequency
It expresses the frequency below which it may be considered that there is zero flow in the system.
It can be set only if FI has been set to operate without a flow sensor. If FI has been set to operate with a flow sensor, the parameter
FZ is blocked. The parameter disabled message is indicated by an icon showing a padlock.
If FZ = 0 Hz is set the inverter will use the self-adaptive operating mode
, instead if FZ ≠ 0 Hz
is set then the inverter will use the
minimum frequency operating mode (see par. 6.5.9.1).
6.5.13
FT: Shutdown threshold setting
This sets a minimum flow threshold, below which, if there is pressure, the inverter stops the electric pump.
This parameter is used in both operation with and without flow sensor, but the two parameters are different; therefore even when the
setting of FI is changed, the FT value remains consistent with the type of operating mode without overwriting the two values. In
operation with the flow sensor, the FT parameter is in litres/minute or gal/min, while without the flow sensor the value is
adimensional.
In the same page, as well as the flow shutdown setting FT, the measured flow rate is displayed, to facilitate user operations. This
appears in a highlighted box below the name of the FT parameter, and bears the text "fl". In operating mode without flow sensor, the
minimum flow “fl” displayed in the box is not immediately available, and may take a few minutes of operation for the figure to be
calculated.
CAUTION: if an excessively high FT value is set, undesired shutdown may occur; if the value is too low operation may be continuous
without stops.
6.5.14
SO: Dry running factor
This sets the minimum dry running factor threshold below which the lack of water is detected. The dry running factor is a non-
dimensional parameter obtained by combining absorbed current and the pump power factor. Thanks to this parameter it is possible
to correctly establish when there is air in the impeller of a pump or if the suction flow is interrupted.
This parameter is used on all multi inverter systems and on all systems without flow sensor. If the pump functions only with one
inverter and flow sensor SO is blocked and disabled.
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...