ENGLISH
109
6.6.13.1
Disabling functions associated with input
If an input is configured at 0, each function associated with this input will be disabled, regardless of the signal on the terminals of the
input itself.
6.6.13.2
Setting the external float function
The external float can be connected to any input, for all electrical connections, refer to paragraph 2.2.4.2. The float function is
implemented by setting the parameter INx associated with the input where the float is connected, with one of the values of Table 23.
Activation of the external float function generates a system block. The function is envisaged to connect the input to a signal from a
float that indicates a water supply failure.
When this function is enabled, the symbol F1 is shown on the STATUS line of the main page.
The input must be activated for at least one second for the system to block and indicate the error F1.
When in the F1 error condition, the input must be deactivated for at least 30 seconds before the system unblocks. The function
behaviour is summarised in Table 23.
When several float functions are configured at the same time on different inputs, the system indicates F1 when at least one function
is activated and clears the alarm when none are activated.
Response of external float function according to setting of INx and input
Parameter
value
INx
Input
configuration
Input status
Operation
Display
1
Active with high signal
on input (NO)
Absent
Normal
None
Present
System block due to lack of
water from external float
F1
2
Active with low signal
on input (NO)
Absent
System block due to lack of
water from external float
F1
Present
Normal
None
Table 23: External float function
6.6.13.3
Setting the auxiliary pressure input function
The auxiliary set points are disabled if the flow sensor is not used (FI=0) and when FZ is used in minimum frequency
mode (FZ ≠ 0).
The signal that enables an auxiliary set point can be supplied on any one of the 4 inputs, (for electrical connections, refer to
paragraph 2.2.4.2). The auxiliary set point function is obtained by setting parameter INx, associated with the input on which the
connection is made, in accordance with Table 24. The auxiliary pressure function modifies the system setpoint from pressure SP
(see section 6.3) to pressure Pi . For electrical connections, see paragraph 2.2.4.2) where i represents the input used. In this way,
as well as SP there are four additional pressures available: P1, P2, P3, and P4.
When this function is enabled, the symbol Pi is shown on the STATUS line of the main page.
The input must be active for at least 1 second for the system to operate with the auxiliary setpoint. When operating with the auxiliary
setpoint, the input must not be active for at least 1 second to return to operation with setpoint SP. The function behaviour is
summarised in Table 24. If several auxiliary pressure values are configured at the same time on different inputs, the system indicates
Pi when at least one function is activated. For simultaneous activations, the pressure reached will be the lowest from those with the
input active. The alarm is cleared when no input is activated.
Response of auxiliary pressure function according to setting of INx and input
Parameter
value
INx
Input
configuration
Input status
Operation
Display
3
Active with high signal
on input (NO)
Absent
Auxiliary set point of same
name not active
None
Present
Auxiliary set point of same
name active
Px
4
Active with low signal
on input (NO)
Absent
Auxiliary set point of same
name active
Px
Present
Auxiliary set point of same
name not active
None
Table 24: Auxiliary setpoints
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...