ENGLISH
100
On initial start-up and when default settings are restored, FN is set at 50 [Hz] and the correct value must be entered, as
stated on the pump
.
Each modification to FN is interpreted as a system change, and therefore the parameters FS, FL and FP are adjusted automatically
according to the set FN. On each variation to FN re-check FS, FL, FP to ensure settings are as required.
6.5.4
OD: Type of system
Set with two possible values (1 and 2) according to a rigid or flexible system.
The inverter leaves the factory set to mode 1, suited to most systems. In the event of pressure variations that cannot be stabilised by
adjusting parameters GI and GP, switch to mode 2.
IMPORTANT:
In the two configurations, the values of adjustment parameters
GP
and
GI
also change. Furthermore, the values
of GP and GI set in mode 1 are stored in a different memory from the GP and GI values set in mode 2.
Therefore, for example, the value of GP in mode 1, when switching to mode 2, is replaced by the GP value of
mode 2, but is stored and restored on return to mode 1. The same value seen on display has a different meaning
in each of the modes, as the check algorithm is different.
6.5.5
RP: Setting the pressure drop for restart
This shows the drop in pressure, with respect to the value SP which causes pump restart.
For example, if the setpoint pressure is 3.0 [bar] and RP is 0.5 [bar] the pump is restarted at 2.5 [bar].
RP is normally set from a minimum of 0.1 to maximum 5 [bar]. In special conditions (for example in the case of a setpoint lower than
RP) this can be limited automatically.
To facilitate the work of the user, the RP setting page, highlighted below the symbol RP, shows the effective restart pressure; see
Figure 17.
Figure 17: Setting the restart pressure
6.5.6
AD: Address configuration
This is only applicable on multi-inverter systems. It sets the communication address to be assigned to the inverter. The possible
values are: automatic (default), or manually assigned address.
The manually assigned addresses can have values from 1 to 8. Configuration of the addresses must be uniform for all inverters in
the series: either all automatic or all manual. Identical addresses are not admitted.
If the address assignment modes are mixed (some manual and some automatic), and also if an address is duplicated, the relative
error is shown. The error is indicated with a flashing “E” in place of the unit address.
If selected assignment is automatic, each time the system is turned on, the addresses are assigned automatically and may be
different from the previous time; this has no effect on correct operation.
6.5.7
PR: Pressure sensor
Setting of the type of pressure sensor used. This parameter enables selection of a ratiometric or current type pressure sensor. For
each type of sensor, different full scales can be selected. When a ratiometric sensor is selected (default) the input Press 1 must be
used for connection. When a 4-20mA current sensor is used, the relative screw terminals on the input terminal board must be used.
(See Collegamento del sensore di pressione par 2.2.3.1)
Summary of Contents for PWM 201
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 73: ...ENGLISH 71 Figure 2 Fixture and minimum clearance for air circulation...
Page 129: ...FRAN AIS 127 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 185: ...DEUTSCH 183 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 244: ...ESPA OL 242 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 295: ...293 IEC 60634...
Page 296: ...294 1 6 1 1...
Page 300: ...298 1 2 5 2 1 2 1 2 2...
Page 301: ...299 2...
Page 302: ...300 2 2 3 3 15 2 2 1 4 2 2 1 1 PWM 203 202 201 3 1 LN 4 2 3...
Page 306: ...304 6 2 2 3 3 Press e Flow 7 A B C D...
Page 311: ...309 DC AC 50 60 8 6 2 1 5 36 36 12 3 3 3 3 2 13 7 11 8 11...
Page 313: ...311 9 MODE 1 SET 9 3 EEprom SET 6 SET MODE 3 1 11 3 2 1 2 3 2 1 MODE SET MODE 10...
Page 315: ...313 SO AE MP I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 RF PW 11 3 2 2 13 SET 13 15 14...
Page 316: ...314 14 3 3 12 GO SB BL LP HP EC OC OF SC OT...
Page 318: ...316 4 4 1 Link 8 4 2 4 2 1 Link Link 16...
Page 322: ...320 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL 4 5 1 4 5 1 1 ET ET ET ET 0 ET 6 6 9 4 5 1 2 23 23...
Page 359: ...NEDERLANDS 357 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 418: ...SVENSKA 416 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 473: ...T RK E 471 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 523: ...520 IEC 364 inverter...
Page 524: ...521 1 Inverter inverter inverter 6 inverter 1 1...
Page 528: ...525 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 529: ...526 2...
Page 534: ...531 6 2 2 3 3 Press Flow 7 A B C D...
Page 539: ...536 DC V AC 50 60 Hz Vrms V 8 6 V 2 1 5 V 36 36 12V mA 3 3 3 3 mm 2 13 7 11 8...
Page 545: ...542 14 3 3 go Hz bar psi 12 GO SB BL LP HP EC OC OF SC OT...
Page 588: ...ROM N 585 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 635: ...01 20 cod 60198807...