InteliMains 210 Global Guide
515
Alarm Type
History record
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right voltage between phases L2 a L3. The following
setpoints are related to it:
Bus Right Overvoltage (page 182)
Bus Right < > Voltage Delay (page 183)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph3Wire or High Leg D.
Bus Right L2L3 Overvoltage
back to List of alarms level 2
Alarm Type
History record
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right voltage between phases L2 a L3. The following
setpoints are related to it:
Bus Right Undervoltage (page 183)
Bus Right < > Voltage Delay (page 183)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph3Wire or High Leg D.
Bus Right L2L3 Undervoltage
back to List of alarms level 2
Alarm Type
History record
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right phase voltage in phases. The following
setpoints are related to it:
Bus Right Overvoltage (page 182)
Bus Right < > Voltage Delay (page 183)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph4Wire.
Bus Right L3 Overvoltage