InteliMains 210 Global Guide
375
Value group
Power Management
Related FW
2.0.0
Units
%
Comm object
10788
Related applications
MCB, MGCB, BTB
Description
Actual relative reserve in power management.
Actual Relative Reserve
Value group
Power Management
Related FW
2.0.0
Units
kW
Comm object
15806
Related applications
MCB, MGCB, BTB
Description
Actual absolute reserve for start.
Start Reserve
Value group
Power Management
Related FW
2.0.0
Units
kW
Comm object
15807
Related applications
MCB, MGCB, BTB
Description
Actual absolute reserve - when the reserve is higher than this value the last started gen-set (the gen-set with
the highest priority) is stopped.
Stop Reserve
Value group
Power Management
Related FW
2.0.0
Units
%
Comm object
10786
Related applications
MCB, MGCB, BTB
Description
Actual relative reserve for start.
Start Relative Reserve
Value group
Power Management
Related FW
2.0.0
Units
%
Comm object
10787
Related applications
MCB, MGCB, BTB
Description
Actual relative reserve - when the relative reserve is higher than this value the last started gen-set (the gen-
set with the highest priority) is stopped.
Stop Relative Reserve