InteliMains 210 Global Guide
176
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
1 .. 2 000 [A/5A]
Default value
500 A/5A
Alternative config
NO
Step
1 A/5A
Comm object
8274
Related applications
MCB, MGCB, BTB
Description
Bus current transformers ratio.
Note:
Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
Bus Import CT Ratio
Subgroup: Voltage settings
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
11628
Related applications
MCB, MGCB
Description
Connection type:
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D
High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
3Ph4Wire
Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
Connection type