InteliMains 210 Global Guide
177
3x CT (Current Transformer)
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
80 .. 20 000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
8277
Related applications
MCB, MGCB, BTB
Description
Nominal voltage (phase to neutral).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-N 2 (page 296)
and
Nominal Voltage Ph-N 3 (page 298)
.
Nominal Voltage Ph-N
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
80 .. 40 000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
11657
Related applications
MCB, MGCB, BTB
Description
Nominal system voltage (phase to phase).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-Ph 2 (page 297)
and
Nominal Voltage Ph-Ph 3 (page 299)
Nominal Voltage Ph-Ph
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9579
Related applications
MCB, MGCB, BTB
Description
Bus voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
Bus VT Ratio