InteliMains 210 Global Guide
294
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW
2.0.0
Range [units]
0 .. 65 535[-]
Default value
23
Alternative config
NO
Step
[-]
Comm object
24374
Related applications
MCB, MGCB, BTB
Description
This setpoint is used to adjust the port number, which is used for Ethernet connection to a PC with any of
ComAp PC program (i.e. InteliConfig). This setpoint should be adjusted to 23, which is the default port used
by all ComAp PC programs. A different value should be used only in special situations as e.g. sharing one
public IP address among many controllers or to overcome a firewall restrictions.
IMPORTANT: If AirGate is used, this setpoint has to be adjusted to 23.
Note:
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
ComAp TCP Port
Group: Alternate Configuration
Subgroup: Configuration 1
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
9913
Related applications
MCB, MGCB, BTB
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
This value is used when any other alternate configuration is not active.
Nominal Frequency 1
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
80 .. 20000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
12052
Related applications
MCB, MGCB, BTB
Description
Nominal system voltage (phase to neutral).
Note:
This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-N 1