InteliMains 210 Global Guide
562
Binary outputs LEDs
8 LEDs for binary output indication
CAN LED
Indication transmitted or received data
Status
LED indication of correct function
CAN terminator
Terminating CAN resistor (active in position “ON” - switch both switches)
Inputs and outputs
Binary inputs
8 channels
can be configured as:
pull up
pull down
All 8 inputs are configured to one type together.
All inputs can be configured to any logical function or protection.
Binary outputs
8 channels
can be configured as:
High side switch
Low side switch
Always all 8 inputs are configured to one type (HSS/LSS) together. All 8 outputs can be modified to inputs by
switch on the PCB ( Inteli IO8/8 to Inteli IO16/0).
Analog outputs
2 channels
can be configured as:
voltage 0-10V
current 0-20mA
PWM (level 5V, with adjustable frequency from 200Hz to 2400Hz, with step 1Hz)
All inputs/outputs can be configured to any logical function or protection.
Output state check
Output state check function evaluates in real time the state of binary outputs and adjusted (required) state. In
case of failure (different state of required state and real state) history record and alarm are issued (type of the
alarm is set by “Protection upon module failure” - (No protection / Warning / Shutdown)).
This function is designed for short-circuit or other failure, which causes change of set state of binary output.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.