InteliMains 210 Global Guide
94
System
Load [kW]
Running gen-sets
Description
Total Running power
within PM [kW]
Relative load
of gen-sets [%]
840
1
4
2
3
900
93
880
1
4
2
3
5
5 start
Gen#5 joins (LDS)
1000
88
940
1
4
2
3
5
1000
94
Minimal running power
Minimum Running Power function is used to adjust a minimum value of the sum of nominal power of all running
gen-sets. If the function is active, then the gen-sets would not be stopped, although the reserve for stop is
fulfilled. Function is activated via logical binary input