InteliMains 210 Global Guide
508
Alarm Type
Warning
Alarmlist message
Wrn Battery Voltage
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm informs the operator that the controller supply voltage is out of limits.
The following setpoints are related to it:
Battery Undervoltage (page 180)
Battery Overvoltage (page 180)
Battery <> Voltage Delay (page 181)
Wrn Battery Voltage
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
Event Email 1 Fail
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm indicates that there was a request to send an event email to email
address which is adjusted in setpoint
and email wasn’t
send.
Event Email 1 Fail
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
Event Email 2 Fail
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm indicates that there was a request to send an event email to email
address which is adjusted in setpoint
and email wasn’t
send.
Event Email 2 Fail
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
Event Email 2 Fail
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm indicates that there was a request to send an event email to email
address which is adjusted in setpoint
and email wasn’t
send.
Event Email 3 Fail