InteliMains 210 Global Guide
245
General Analog Input 20
Setpoint group
General Analog Inputs
Related FW
2.0.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
9316
Related applications
MCB, MGCB, BTB
Description
Warning or history threshold level for
.
Note:
These setpoints are used only if LAI
is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 20 Wrn
Setpoint group
General Analog Inputs
Related FW
2.0.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
9317
Related applications
MCB, MGCB, BTB
Description
Shutdown or BOC threshold level for
.
Note:
These setpoints are used only if LAI
is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 20 Sd
Setpoint group
General Analog Inputs
Related FW
2.0.0
Range [units]
0 .. 900 [s]
Default value
0 s
Alternative config
NO
Step
1 s
Comm object
9318
Related applications
MCB, MGCB, BTB
Description
Delay for
Note:
These setpoints are used only if LAI
is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 20 Delay