InteliMains 210 Global Guide
428
LBI: E
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
45
Description
This input is designed to allow the gen-set or breakers to be controlled externally, not by the controller. This
feature can be useful in case of or in case of some failure, which disables the gen-set or breakers to be
controlled by the controller, but the gen-set itself is operational.
The controller behaves in the following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the gen-set or breaker control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is detected.
When the input is deactivated, the controller takes control according to the situation in the moment of
deactivation.
Emergency MAN
back to Logical binary inputs alphabetically
LBI: F
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
191
Description
Binary input has the same function as Fault Reset button
on the InteliMains 210 front panel.
Fault Reset Button
back to Logical binary inputs alphabetically
Related FW
2.0.0
Related applications
BTB
Comm object
952
Description
Close BTB regardless on the setpoint setting. Synchronize both sides regardless on the setpoints setting.
IMPORTANT: Setpoint
has higher priority than this LBI.
Note:
When LBI is active, BTB can be opened only due to BTB open protection or BTB Fail.
Force BTB Close