Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a
new alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms on binary or analog inputs
Controller built-in alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC,
Stp, MP, MPR). Then the alarm name follows. In some cases the prefix can be omitted.
User configured alarms
An alarm message in the alarmlist begins with a prefix, which represents the alarm type (e.g. Wrn, Sd, BOC,
MP, MPR). Alarm type is selected by user during the configuration of binary or analog input as alarm. Then the
alarm name follows. Name is adjusted by user during the configuration of binary or analog input as alarm.
Built-in alarms
Events
specification
Protection
type
Description
Wrn Battery Voltage
WRN
Battery voltage is out of limits given by
and
Battery Overvoltage (page 180)
setpoints.
Binary input
Configurable Warning/MP/MPR alarms on the binary inputs.
RTC Battery Flat
WRN
RTC battery weak or flat and has to be changed.
Parameters Fail
NONE
Wrong check-sum of parameters. Happens typically after downloading
new firmware or changing of the parameter. The controller stays in
INIT mode. Check all parameters, change value of at least one
parameter.