InteliMains 210 Global Guide
410
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
9983
Description
This binary input is for general input function used as alarm.
Monitoring
Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl
Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic
Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn
Binary input is used for warning protection only.
BO
Breaker open protection without reset. Protection is signalized with red LED status
but the alarm is not in alarm list.
BOR
Breaker open protection with reset. Protection is signalized with red LED status
and alarm is recorded in alarm list.
FLS
Sensor fail protection.
Protection types
BIN Protection 17
back to Logical binary inputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
9982
Description
This binary input is for general input function used as alarm.
Monitoring
Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl
Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic
Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn
Binary input is used for warning protection only.
BO
Breaker open protection without reset. Protection is signalized with red LED status
but the alarm is not in alarm list.
BOR
Breaker open protection with reset. Protection is signalized with red LED status
and alarm is recorded in alarm list.
FLS
Sensor fail protection.
Protection types
BIN Protection 18