InteliMains 210 Global Guide
284
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW
2.0.0
Range [units]
0 .. 65 535[-]
Default value
23
Alternative config
NO
Step
[-]
Comm object
24374
Related applications
MCB, MGCB, BTB
Description
This setpoint is used to adjust the port number, which is used for Ethernet connection to a PC with any of
ComAp PC program (i.e. InteliConfig). This setpoint should be adjusted to 23, which is the default port used
by all ComAp PC programs. A different value should be used only in special situations as e.g. sharing one
public IP address among many controllers or to overcome a firewall restrictions.
IMPORTANT: If AirGate is used, this setpoint has to be adjusted to 23.
Note:
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
ComAp TCP Port
Group: CM-Ethernet
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW
2.0.0
Range [units]
0..63 characters [-]
Default value
[-]
Alternative config
NO
Step
[-]
Comm object
24298
Related applications
MCB, MGCB, BTB
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note:
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 1