These LBI functions are shared automatically:
System Start/Stop
Note:
InteliMains controller activates the System Start/Stop signal in case of all system activations (e.g. AMF,
TEST Mode, ...)
Min Run Power Act
Load Res 2 Active
MCB Feedback
These rules applies to the automatic sharing of the selected signals:
1. LBI state is automatically shared via CAN2 bus, if corresponding LBI function is configured in a controller.
Example:
Logical input Remote Start/Stop is configured with a controller. State of the signal is
automatically transmitted to other controllers via CAN2 bus as System Start/Stop.
2. LBI state received from CAN2 bus is automatically used, if corresponding LBI function is not configured in a
controller.
Example:
LBI Remote Start/Stop is not configured with a controller, but automatically shared
System Start/Stop is received from CAN2 bus. Controller follows state of the shared LBI signal then.