InteliMains 210 Global Guide
173
Setpoint group
Process
Control
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
16048
Related applications
BTB
Description
Setpoint for adjustment of the direction of synchronization. This setpoint has to be Enable for situations
where the Mains is on the right side and gen-sets are on the left side.
Note:
In case the Mains is on the left side, the controller will not try to synchronize.
Synchronization L To Mains
Setpoint group
Process
Control
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
16049
Related applications
BTB
Description
Setpoint for setting the direction of synchronization. This setpoint has to be set to Enable if on both sides are
gen-sets. In case the setpoint is set to enable and even on one side is mains, controller recognizes it and
automatically adjust the direction of synchronization.
Synchronization R To L
Setpoint group
Process
Control
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
16050
Related applications
BTB
Description
Setpoint for setting the direction of synchronization. This setpoint has to be set to Enable if on both sides are
gen-sets. In case the setpoint is set to enable and even on one side is mains, controller recognizes it and
automatically adjust the direction of synchronization.
Synchronization L To R