InteliMains 210 Global Guide
158
Password
This password is the same as in InteliConfig or directly in controller.
Table
Register addresses
Number of registers
Access
Data type
Meaning
4211
1
write
Unsigned16
Password
Note:
Default password is "0".
In this example the password is "1234".
Request: (Numbers in Hex)
01
06
10
73
04
D2
7C
D1
Controller address
Modbus function
Register address
1073
hex
=
4211
dec
Password
04D2
hex
=
1234
dec
CRC
Response for success: (Numbers in Hex)
01
06
10
73
00
00
7C
D1
Controller address
Modbus function
Register address
1073
hex
=
4211
dec
Allways zero.
CRC
Response for bad password: (Numbers in Hex)
01
86
04
43
A3
Controller
address
Modbus exception
for function 6.
04 – device error
see Error codes (exception codes) on page 151
CRC