InteliMains 210 Global Guide
295
Setpoint group
Related FW
2.0.0
Range [units]
80 .. 40000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
12055
Related applications
MCB, MGCB, BTB
Description
Nominal system voltage (phase to phase).
Note:
This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-Ph 1
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
12049
Related applications
MCB, MGCB, BTB
Description
It is current limit for current protections and means maximal continuous current.
Note:
This value is used when any other alternate configuration is not active.
Nominal Current 1
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire[-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
12058
Related applications
MCB, MGCB, BTB
Description
Connection type:
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire
Ungrounded Delta connection
Open Delta
Ungrounded Wye
Connection Type 1