InteliMains 210 Global Guide
546
35
ME909s: HW reset issued
36
ME909s: can't switch echo off
37
ME909s: can't find out state of registration
38
ME909s: GSM signal not found
39
ME909s: no SIM memory for SMS
40
ME909s: waiting for registration
41
Can't read operator name
42
ME909s: can't set flow control
43
APN not typed
255
Only running communication is needed to indicate
AirGate Diag – Diagnostic Code for AirGate connection
Code
Description
0
Waiting for connection to AirGate Server
1
Controller registered, waiting for authorization
2
Not possible to register, controller blacklisted
3
Not possible to register, server has no more capacity
4
Not possible to register, other reason
5
Controller registered and authorized
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
CM-4G-GPS
CM-4G-GPS plug-in module containing a GPS receiver and GSM/WCDMA/LTE modem which can works in
two modes of operation based on the settings in the setpoint
.