InteliMains 210 Global Guide
564
11. Connect power supply again (status LED should blinking)
12. Module FW is upgraded
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set. When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs. When this
LED is dark, then the module is configured as 16 binary inputs.
LED at power connector - status LED
LED status
Description
Dark
Fw in module does not work correctly.
Flashing
Module does not communicate with controller (in case non-zero CAN address).
Lights
Power supply is in the range and the communication between Inteli IO8/8 and controller
works properly.
Or power supply is in range and zero CAN address is set. (in case zero CAN address
module doesn’t communicate with the controller).
Wiring
The following diagrams show the correct connection of inputs and outputs.
Binary inputs - pull up
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the GND (-) - dashed line).