InteliMains 210 Global Guide
108
Frequency
Bus Right Voltage
Vbr1
Bus Right voltage Ph1
Bus Right Voltage
Vbr2
Bus Right voltage Ph2
Bus Right Voltage
Vbr3
Bus Right voltage Ph3
Bus Right Voltage
Vbr12
Bus Right voltage Ph12
Bus Right Voltage
Vbr23
Bus Right voltage Ph23
Bus Right Voltage
Vbr31
Bus Right voltage Ph31
Bus Left Frequency
Brfrq
Bus Left Frequency
Bus Left Voltage
Vbl1
Bus Left voltage Ph1
Bus Left Voltage
Vbl2
Bus Left voltage Ph2
Bus Left Voltage
Vbl3
Bus Left voltage Ph3
Bus Left Voltage
Vbl12
Bus Left voltage Ph12
Bus Left Voltage
Vbl23
Bus Left voltage Ph23
Bus Left Voltage
Vbl31
Bus Left voltage Ph31
Bus Left Current
IL1
Bus Left current Ph1
Bus Left Current
IL2
Bus Left current Ph2
Bus Left Current
IL3
Bus Left current Ph3
Voltage Battery
VBat
Voltage of battery
Binary Inputs
BIN
Controller binary inputs
Binary Outputs
BOUT
Controller binary outputs
Running nominal
power
TRPN
Nominal power of all running gen-sets
Available nominal
power
APN
Available nominal power of all gen-sets
Controller Mode
Mode
Controller mode
Note:
When some setpoint is changed, in history log is written its number of communication object.
Note:
Some additional columns can be added due to actual controller configuration (modules, etc.).
5.4.12 Breaker control
The following power switches are controlled by the controller:
TheBus Tie breaker or contactor – BTB
It is possible to use either a motorized circuit breaker or contactor. Below is a list of available control outputs
that should fit all types of contactors or breakers. The following rules must be kept to when designing the wiring
of power switches:
The control outputs must be configured and wiring of the power switches must be provided in such a way,
that the controller has full control over the breakers – i.e. the controller can open and close the breaker at any
time.
The breaker must respond within max. 2 seconds to a close and open command. Special attention should be
paid to opening of motorized circuit breakers, as it could take more than 2 seconds on some types. In such
cases it is necessary to use an undervoltage coil for fast opening.