InteliMains 210 Global Guide
510
Alarm Type
Other
Alarmlist message
Event SMS 4 Fail
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm indicates that there was a request to send an event SMS to telephone
number which is adjusted in setpoint
and SMS
wasn’t send.
Event SMS 4 Fail
back to List of alarms level 1
Alarm Type
Alarm indication
Alarmlist message
Bus CCW Rotation
Alarm evaluated
All the time
Related applications
MCB, MGCB
Description
The controller detects phase sequence on bus voltage terminals. This protection is
important after controller installation to avoid wrong voltage phase connection.
There is a fixed defined phase sequence in InteliMains 210 controller: T35 = N, T36
= L1, T37 = L2 and T38 = L3. When the phases are connected in a different order,
alarms are detected. This alarm prevent circuit breaker closing.
Bus CCW Rotation
back to List of alarms level 1
Alarm Type
Alarm indication
Alarmlist message
Bus Left CCW Rotation
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The controller detects phase sequence on Bus Left voltage terminals. This
protection is important after controller installation to avoid wrong voltage phase
connection.
Bus Left CCW Rotation
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn + Name of analog input
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm indicates that value the general analog protection is out of warning
protection limit.
Wrn AIN Prot