InteliMains 210 Global Guide
181
Setpoint group
Engine settings
Related FW
2.0.0
Range [units]
0 .. 600 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8383
Related applications
MCB, MGCB, BTB
Description
Delay for
Battery Undervoltage (page 180)
and
Battery Overvoltage (page 180)
protection.
Battery <> Voltage Delay
Group: Communication Settings
Subgroup: Controller CAN Address
Setpoint group
Communication
Settings
Related FW
2.0.0
Range [units]
1 .. 32 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
24537
Related applications
MCB, MGCB, BTB
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note:
When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Controller Address
Subgroup: RS485 Settings
Setpoint group
Communication
Settings
Related FW
2.0.0
Range [units]
Direct / MODBUS [-]
Default value
Direct
Alternative config
NO
Step
[-]
Comm object
24134
Related applications
MCB, MGCB, BTB
Description
Communication protocol switch for on-board RS485.
Direct
InteliConfig communication protocol via serial cable.
MODBUS
MODBUS protocol.
RS485 Mode