InteliMains 210 Global Guide
182
Setpoint group
Communication
Settings
Related FW
2.0.0
Range [units]
9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value
57600 bps
Alternative config
NO
Step
[-]
Comm object
24135
Related applications
MCB, MGCB, BTB
Description
If the direct mode is selected on on-board RS485, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.
Note:
Winscope supports only 19200, 38400, 57600 speeds.
RS485 Communication Speed
Setpoint group
Communication
Settings
Related FW
2.0.0
Range [units]
9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value
9600 bps
Alternative config
NO
Step
[-]
Comm object
24141
Related applications
MCB, MGCB, BTB
Description
If the MODBUS mode is selected on COM1 channel, the MODBUS communication speed can be adjusted
here.
RS485 MODBUS Speed
Group: Bus Right Settings
Subgroup: Bus Right Voltage Limits
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
Bus Right Undervoltage (page 183)
.. 150 [%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
9686
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Right overvoltage. All three phases are checked. Maximum out of three is used.
Bus Right Overvoltage