Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
50 ..
Bus Right Overvoltage (page 182)
[%]
Default value
60 %
Alternative config
YES
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
9687
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Right undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Bus Right Undervoltage
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
0,0 .. 600,0 [s]
Default value
2,0 s
Alternative config
YES
Step
0,1 s
Comm object
9103
Related applications
MCB, MGCB, BTB
Description
Delay for
Bus Right Undervoltage (page 183)
and
Bus Right Overvoltage (page 182)
protection.
Bus Right < > Voltage Delay
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
1 .. 150 [%] of
Nominal Voltage Ph-Ph (page 177)
Default value
10 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
8288
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Right voltage unbalance.
Bus Right Voltage Unbalance
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
0,0 .. 60,0 [s]
Default value
2,0 s
Alternative config
NO
Step
0,1 s
Comm object
8289
Related applications
MCB, MGCB, BTB
Description
Delay for
Bus Right Voltage Unbalance (page 183)
protection.
Bus Right Voltage Unbalance Delay