2.6.7 RelayPak (Optional)
Model Number: RP100
The RelayPak is used to provide up to four built-in slave relays in a compact and easy to wire package. This
allows the low current outputs of the controller to switch on high current relays on the RelayPak.
Note:
The RelayPak can be used to sense DC voltages up to 39 VDC using one of the Auxiliary Sensor
Inputs on the controller. The VM in RP100-VM refers to this voltage sensing capability. Refer to
drawing DWG1552 at
. If this capability is used, the fourth relay, Relay D, cannot be
used.
Electrical Specifications
Specification
Rating
Operating Voltage
12 V / 24 V
Output Pilot Duty Rating
5.83 A Per Relay @ 12 V
Output Resistive Rating
10 A Continuous Per Relay @ 12 V
40 A Momentary Per Relay @ 12 V
Relay Style
Automotive Cube
Standards
UL 6200 recognized component. Contact Cattron at
for UL conditions of acceptability.
WARNING
YOU MUST USE RELAYS IN THE RELAYPAK THAT ARE SUITABLE FOR THE SYSTEM
VOLTAGE; FOR EXAMPLE, 12 V RELAYS IN A 12 V SYSTEM AND 24 V RELAYS IN A 24 V
SYSTEM.
AVERTISSEMENT
VOUS DEVEZ UTILISER DES RELAIS ADAPTES A LA TENSION DU SYSTEME DANS LE
RELAYPAK. PAR EXEMPLE, DES RELAIS 12 V POUR UN SYSTEME 12 V, ET DES RELAIS 24 V
POUR UN SYSTEME 24 V.
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...