DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
59
9M02-9249-A001-EN
Revision A
CAUTION
WHEN RUNNING WIRES OVER LONG DISTANCES (OVER 20 FT / 6.1 M), IT IS RECOMMENDED
THAT THE +BATTERY BE USED AS THE TRIGGER METHOD.
ATTENTION
LORSQUE VOUS FAITES PASSER DES FILS SUR DE LONGUES DISTANCES (AU DELA DE 6 M),
IL EST RECOMMANDE D'UTBATTERIE COMME METHODE DE DECLENCHEMENT.
5.3.1 Configurable Inputs
These inputs are used to create custom warnings and failures. Using the RapidCore Configurator Software, you
can change the text displayed when the warning or failure occurs. If you select one of these inputs without
changing the text, it will default to
‘Config Warn X’ and ‘Config Fail X’.
There are also timers associated with the configurable inputs which can be found in the menu under Timers >
Trigger Delays > Config Inputs and Config Fail 3. These timers change the amount of time the input has to be
active before the controller registers the warning or failure.
CAUTION
IF THE SWITCHED INPUT BECOMES INACTIVE BEFORE THE TRIGGER DELAY TIME EXPIRES,
THE WARNING OR FAILURE WILL NOT OCCUR.
ATTENTION
SI L'ENTREE COMMUTEE DEVIENT INACTIVE AVANT L'EXPIRATION DU DELAI DE
DECLENCHEMENT, L'AVERTISSEMENT OU LA PANNE NE SE PRODUIRA PAS.
Example:
The user wants a pump to turn on 30 seconds after a high water level switch is tripped and remain on
until the level switch turns off.
The level switch is connected to Switched Input C and closes to ground when the water level is too high. The
words
‘Water Pumping’ are also required to be displayed on the controller’s LCD screen. The pump is connected
to a slave relay which is controlled by Switched Output D on the controller.
Relevant Settings
Setting
Value
Switched Input C > Function
Configurable Warning 1
Switched Input C > Active Mode
Global
Switched Input C > Trigger
Close GND
Configurable Warning 1 Custom Text
Water Pumping
Switched Output D > Warnings
Configurable Warning 1
!
!
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...