CAUTION
SETTING A TIMER’S VALUE TO 0 SECONDS WILL DISABLE THE TIMER. FOR EXAMPLE, IF
DELAY TO START IS SET TO 0 S, THE CONTROLLER WILL NOT PERFORM A DELAY TO START
WHEN STARTING THE ENGINE.
ATTENTION
REGLER LA MINUTERIE SUR 0 SECONDE A POUR EFFET DE LA DESACTIVER. PAR EXEMPLE,
SI DELAY TO START (RETARD AU DEMARRAGE) EST REGLE SUR 0 S, LE CONTROLEUR
N'APPLIQUERA PAS DE RETARD AU DEMARRAGE LORS DU DEMARRAGE DU MOTEUR.
Timers > Engine Logic:
Name
Range
Default
Description
Delay to Start
0 ~ 90 s
0 s
Amount of time to delay the starting of the
engine after receiving a command to start.
DTS Manual Run
(Delay to Start on
Manual Run)
Disable Delay or
Enable Delay
Enable Delay
Determines if the Delay to Start timer is
used when the front panel RUN button is
used to start the engine.
Preheat Timer
Switched Input
J1939
Preheat Timer
Determines the method used to control
enabling the Glowplug output. See the
Preheat Mode
section for more
information.
Preheat Time
0 ~ 1200 s
0 ~ 90 s in
firmware versions
below 1.33
0 s
Amount of time the Glowplug output is
active before cranking the engine. Used on
diesel engines to warm the engine before
cranking.
Crank Time
3 ~ 30 s
10 s
Amount of time the Crank output is active
before going to crank rest. This timer
immediately expires upon successful
cranking.
Midheat Time
0 ~ 90 s
0 s
Keeps Glowplug output turned on while
cranking but not during crank rest. Output
will turn off upon crank failure, crank
success or midheat time expiration.
Crank Rest Time
1 ~ 90 s
15 s
Amount of time to delay between each
attempt to start the engine.
Crank Attempts
1 ~ 20
3
Number of attempts to start the engine
before going to an overcrank failure.
Fuel In Rest (Fuel
Crank Rest)
Fuel ON or
Fuel OFF
Fuel ON
Determines if the fuel output stays on
during the crank rest time.
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...