DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
74
9M02-9249-A001-EN
Revision A
CAUTION
WHEN USING SWITCHED OUTPUTS FOR SPEED CONTROL, THE SET RPM WILL DISPLAY '---'
INSTEAD OF THE SET SPEED.
ATTENTION
SI VOUS UTILISEZ DES SORTIES COMMUTEES POUR LA COMMANDE DE VITESSE, SET RPM
(REGIME MOTEUR DE CONSIGNE EN TOURS/MINUTE) AFFICHERA « --- » AU LIEU DU REGIME
DE CONSIGNE.
5.5.5 Battery
Use the following settings
’ configurations to allow the controller to read and interpret the battery voltage level.
Name
Range
Default
Description
Battery Recharge
Enable
Disable
Disable
Enables or disables the ability to have the engine
start on low battery voltage in order to charge it.
Recharge Setup
> Level
6.0 - 30.0 V
10.4 V
Voltage level at which the controller starts the
engine to recharge the battery.
Recharge Setup
> Pre-Alarm
1 ~ 30 min
5 min
Amount of time to display a warning before
starting the engine.
Recharge Setup
> Duration
10 ~ 900 min
90 min
Amount of time to run the engine.
Setpoints > Low
Warning
Disabled
6.0 ~ 24.0 V
11.3 V
Reading at which a warning occurs.
Setpoints > Low
Failure
Disabled
6.0 ~ 24.0 V
Disabled
Reading at which a failure occurs.
Setpoints > High
Warning
Disabled
12.0 ~ 32.0 V
Disabled
Reading at which a warning occurs.
Setpoints > High
Failure
Disabled
12.0 ~ 32.0 V
Disabled
Reading at which a failure occurs.
LowBat InCrank
6.0 ~ 24.0 V
8.0 V
Screen displays a
‘Low Voltage During Cranking’
warning if voltage dips below this level during
cranking.
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...