DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
80
9M02-9249-A001-EN
Revision A
Behavior
Func.
Select
Start Level
Run Time
Stop Level
A -
Indefinitely
Start controller when the
sensor drops below a
certain value. Run
indefinitely.
1
Start on
Low
Set to value that
the sensor needs
to drop below to
start.
Disable
Disable
Turn on an output when
the sensor drops below a
certain value. Keep the
output on indefinitely.
2
Output
on Low
Set to value that
the sensor needs
to drop below to
turn on the
output.
Disable
Disable
Start controller when the
sensor rises above a
certain value. Run
indefinitely.
1
Start on
High
Set to value that
the sensor needs
to rise above to
start.
Disable
Disable
Turn on an output when
the sensor rises above a
certain value. Keep the
output on indefinitely.
2
Output
on High
Set to value that
the sensor needs
to rise above to
turn on the
output.
Disable
Disable
B -
Fixed
Duration
Start controller when the
sensor drops below a
certain value. Run for a
fixed period of time and
then stop controller.
Start on
Low
Set to value that
the sensor needs
to drop below to
start.
Set to the
desired run
duration.
Disable
Turn on an output when
the sensor drops below a
certain value. Run for a
fixed period of time and
then turn off the output.
Output
on Low
Set to value that
the sensor needs
to drop below to
turn on the
output.
Set to the
desired
duration to
keep the
output on.
Disable
Start controller when the
sensor rises above a
certain value. Run for a
fixed period of time and
then stop controller.
Start on
High
Set to value that
the sensor needs
to rise above to
start.
Set to the
desired run
duration.
Disable
Turn on an output when
the sensor rises above a
certain value. Run for a
fixed period of time and
then turn off the output.
Output
on High
Set to value that
the sensor needs
to rise above to
turn on the
output.
Set to the
desired
duration to
keep the
output on.
Disable
C -
Start Level
/ Stop
Level
Start controller when the
sensor drops below a
certain value. Stop
controller when the
sensor rises above a
certain value.
Start on
Low
Set to value that
the sensor needs
to drop below to
start.
Disable
Set to the value
the sensor
needs to rise
above to stop
the controller.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...