DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
8
9M02-9249-A001-EN
Revision A
Specification
Rating
Weight
Weight w/RelayPak
0.83 lb (0.38 kg)
1.32 lb (0.60 kg)
Dimensions:
-
controller (no gasket)
-
controller with gasket
-
controller with gasket and RelayPak
4.17
” x 6.50” x 1.38” (10.59 cm x 16.51 cm x 3.51 cm)
4.41
” x 6.79” x 1.38” (11.20 cm x 17.25 cm x 3.51 cm)
4.41
” x 6.79” x 3.33” (11.20 cm x 17.25 cm x 8.46 cm)
Electrical Specifications
Specification
Rating
Operating Voltage
5.5 ~ 36 VDC
Standby Current (Minimum)
Auto Mode: 60 mA @ 12 VDC, 38 mA @ 24 VDC (back lighting
off)
Off Mode: 80 mA @ 12 VDC, 45 mA @ 24 VDC (back lighting off)
Actual consumption could be more depending on connected
sensors and other I/O.
Switched Inputs
+Battery, Ground, Open, Closed
Switched Outputs
+Battery @ 1 A Max
Low Resistance Sensors
0 ~ 750
Ω
High Resistance Sensors
0 ~ 7,500
Ω
Universal Sensors
0 ~ 750
Ω, 0 ~ 7,500 Ω, 0 ~ 5 VDC, 4 ~ 20 mA
Magnetic Pickup
10 ~ 10,000 Hz at 1 ~ 50 VAC
AC Voltage (Line-To-Line)
UL Approved Range: 50 ~ 600 VAC True RMS, Accuracy: 2%
Full Scale
Non-UL Range: 50 ~ 670 VAC
Do not connect more than 600 VAC to the controller for UL
approved installations, or 700 VAC for locations where UL is not
required.
AC Current
0 ~ 5 A (Current Transformer), Accuracy: 1% Full Scale
Communications
SAE J1939 (Tier II, III, IV)
External Sensor Power
TG410 only: 5 VDC at a max load of 200 mA
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...