User Manual
102
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
Auto Rated >
1Ph 3-Wire
5 ~ 5000 A
in 1 A increments
100 A
Rated Amps when using the
Auto Rated >
3-Phase (1)
5 ~ 5000 A
in 1 A increments
100 A
Auto Rated >
3-Phase (2)
5 ~ 5000 A
in 1 A increments
100 A
Auto Rated >
3-Phase (3)
5 ~ 5000 A
in 1 A increments
100 A
Auto Scaling >
1Ph 3-Wire
0.500 ~ 2.500
in 0.001 increments
1.000
Scaling Factor when using the
Auto Scaling >
3-Phase (1)
0.500 ~ 2.500
in 0.001 increments
1.000
Auto Scaling >
3-Phase (2)
0.500 ~ 2.500
in 0.001 increments
1.000
Auto Scaling >
3-Phase (3)
0.500 ~ 2.500
in 0.001 increments
1.000
Dummy Load
[Menu]
Basic Alarm
[Menu]
IDMT Protect
Disable
Breaker Trip
Shutdown Trip
IDMT Settings
[Menu]
Imbalance Mode
Disable
Breaker Trip
Shutdown Trip
Imbalance Set
[Menu]
Break Trip Fail
Disable
Enable
Disable
Shuts down the generator if the generator
circuit breaker fails to trip.
If the
switched output is active - due to
- and if after 10
seconds the measured generator current is
still above 10% of the Rated Current, the
generator will shut down.
5.7.3.1
Basic Alarms
The controller can give a warning and/or shut down on over current. If
is enabled, then it overrides the
High Failure shutdown, but the warning is still active.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...