DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
77
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
Active Mode
Disable
Global
Off Mode (Not in
Auto)
Auto Mode
Running
Cranking
After Cranking
Cooldown
-----
Determines under which operating conditions the
Auxiliary Sensor is monitored. Multiple selections
are allowed. Does not apply to
“Start on Low” or
“Start on High”; for those selections, the active
mode is always Auto.
Refer to the examples in the following pages for
information on specific mode functions.
-
Disable - Input cannot be triggered
-
Global - Input can be triggered at any time
-
Off Mode - Input can be triggered while in the
Off Mode
-
Auto Mode - Input can be triggered while in
the Auto Mode
-
Running - Input can be triggered after a start
command is received until shutdown
(cooldown not included)
-
Cranking - Input can be triggered during
cranking
-
After Cranking - Input can be triggered after
engine has started until shutdown
-
Cooldown - Input can be triggered while
cooldown timer is active
Func. Select
-----
Determines how the controller responds to the
readings of the Auxiliary Sensor.
“x on Low” will turn on the output or start the
controller if the sensor input falls below the Start
Level.
“x on High” will turn on the output or start the
controller if the sensor input rises above the Start
Level.
Trim Offset
-50.0 ~ 50.0 units
The units depend on
the unit type of the
programmed sender
table -- °F, PSI, %,
V, A
-----
Calibrate a sensor by using the offset to correct
errors.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...