5.5.3 Fuel Level
Use the following settings
’ configurations to allow the controller to read and interpret data from the fuel level
sensor.
Name
Range
Default Settings
Description
Signal Source
Disable
Port A
Port B
Port C
Port D
Disable
The sensor input pin where the fuel level
switch or sender is attached
Sensor Type
DAT R/33-240*
VDO R/0-180*
(custom sender)**
Close =
Open =
Close =
Open =
Close = Failure
Select the sender that is connected to the
Signal Source above. If using a switch,
select the action that should occur when
the switch is active.
*These are preprogrammed into the
controller and cannot be changed.
-
DAT R/33-240 supports a Datcon
fuel level sensor of the range 33
Ω
to 180
Ω
-
VDO R/0-180 supports a VDO fuel
level sensor of the range 0
Ω to
180
Ω
DAT R/33-240 and VDO R/0-180 cannot
be used on port A. To use on port A, store
as a custom sender table using the
RapidCore Configurator software.
**A custom table created using the
RapidCore Configurator Software. The
text (custom sender) will be replaced
with the custom text you choose when
creating the sender.
+The switch must close to ground
Trim Offset
-50.0 ~ 50.0%
0.0%
Calibrate a sensor by using the offset to
correct errors. Only applies if Sensor Type
has been set to a sender.
Setpoints > Bypass
Time
0 ~ 90 s
30 s
Amount of time to bypass warnings and
failures after engine has started.
Setpoints > Low
Warning
Disabled
1 ~ 90%
25%
Reading at which a
“Low Fuel Level”
warning occurs. Only applies if Sensor
Type has been set to a sender. Only
monitored in the Run Mode.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...