Behavior
Func.
Select
Start Level
Run Time
Stop Level
Turn on an output when
the sensor rises above a
certain value. Turn off
output when the sensor
drops below a certain
value. Turn off the output
after a fixed time if the
stop level is not reached.
Output
on High
Set to value that
the sensor needs
to rise above to
turn on the
output.
Set to the
desired
maximum
duration to
keep the
output on (i.e.,
this is the
timeout).
Set to the value
the sensor
needs to drop
below to turn
off the output.
E -
Warnings
/
Failures
Trigger warnings and/or
failures on the sensor.
Fault
Monitor
N/A
N/A
N/A
F -
Display
only
Do not perform any
actions based on the
sensor value. Just display
the value to the user.
Fault
Monitor
(Disable
all
warnings
and
failures)
N/A
N/A
N/A
1
The user must manually stop the controller by pressing the OFF button.
2
The controller must be either
•
Powered down, or
•
A reset initiated by
o
Going from the Run Mode to the Auto or Off Mode, or
o
Changing a setting in the menu and exiting the menu system
5.5.6.1
Fault Monitor Example
In this example, a sensor is monitoring the temperature of an engine block. If the temperature rises above
275 °F, a warning message is displayed. If the temperature rises above 350 °F, the engine shuts down and a
failure message is displayed.
Relevant Settings
Setting
Value
Signal Source
Same as Engine Temperature
Display
Disable (if enabled, controller will display Engine Temperature twice)
Sensor Type
Same as Engine Temperature
Sensor Table Name
Engine Temp.
Active Range
Running
Mode Select
Fault Monitor
Setpoints > Low Warning
Disabled
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...