DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
97
9M02-9249-A001-EN
Revision A
The maintenance counter is disabled if
“---” is displayed. A negative number indicates the amount of time since
the maintenance timer expired.
Note:
The maintenance timer displays
“Service Required” when this time expires. This message is only
displayed the next time the controller enters the Run Mode. If the timer expires when the controller is
in the Run Mode, the message is not displayed.
5.7
AC Monitor
The controller has the ability to monitor AC voltage from a generator. The following sections are used to
configure settings associated with AC monitoring.
5.7.1 Generator Voltage
The following settings are used to configure the controller
’s response to voltage measurements.
AC Monitor > Genset Voltage menu
Name
Range
Default
Description
Voltage Source
Disable
2-Wire Single
3-Wire Single
3-Wire 3-Phase
4-Wire 3-Phase
4-Wire Delta
Auto Selection
3-Wire Single
The wiring configuration of the generator.
Disable will disable AC voltage and AC
frequency sensing and display.
2-Wire Single: One 120 VAC L-N. Use
phase A.
3-Wire Single: 120/240 VAC systems. Use
phases A and B.
3-Wire 3-Phase: Three phase delta without
a ground.
4-Wire 3-Phase: Three phase Wye system.
Center taped ground.
4-Wire Delta: Delta with a ground. The high
leg is phase B. For example, if A-N and C-N
read 120 VAC, then B-N will read 208 VAC.
Auto Selection: Selecting Auto Selection will
use the
switched inputs
to determine the wiring configuration.
This setting also enables the
monitoring and display.
Scaling Factor
0.500 ~ 2.500
in 0.001 increments
1.000
The gain to apply to the AC voltage that is
read at the controller. See below for more
information.
Nominal Volts
50 ~ 800 VAC*
in 1 VAC increments
240 VAC
Generator line-to-line voltage output when
operating under normal running conditions.
Auto Nominal >
1Ph 3-Wire
(1-Phase 3-Wire)
50 ~ 800 VAC*
in 1 VAC increments
240 VAC
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...