Setting
Value
Setpoints > Low Failure
Disabled
Setpoints > High Warning
275 °F
Setpoints > High Failure
350 °F
The following chart shows the connection between engine temperature and time. At approximately 13 minutes
run time, the temperature rises above the 275 °F warning threshold, activating the warning display. The engine
will continue to run because it has not reached the 350 °F failure threshold. At 20 minutes run time, the
temperature falls below the warning threshold, and the warning disappears.
5.5.6.2
Start on Low Example
In this example, a sensor is monitoring the voltage of an external battery bank. If the voltage falls below 10.5 V,
the engine will start and run for 40 minutes to charge the battery.
Relevant Settings
Setting
Value
Signal Source
Sensor Port X
Display
Enable
Sensor Type
Custom
Sensor Table Name
Battery Bank
Active Range
N/A (these ranges are fixed for Start on Low / High)