Tank Maximum >
Max %
Disable
0 ~ 100%
in 0.1% increments
These settings determine the maximum Aux Sensor
value that is equivalent to a full tank. If the sensor
value rises above these setpoints, then the value
displayed in the tank is clamped to these settings.
Used by the
sender in the
Application menu.
Tank Maximum >
Max PSI
Disable
0 ~ 100 PSI
in 0.1 PSI increments
Tank Maximum >
Max Foot
Disable
0 ~ 100 ft
in 0.1 ft increments
RPM Display
Blank
AC Hertz
Aux Sensor 1
Aux Sensor 2
This is a replication of the
“RPM Display” setting in
the Sensors > Engine Speed menu.
RPM Setting
Sub menu
-----
RPM Setting >
Min Speed
500 ~ 4000 RPM
in 1 RPM increments
These are a replication of the RPM Setting menu
under the Sensors > Engine Speed menu.
The first three control the minimum and maximum
values to which the engine speed can be adjusted.
The TSC1 RPM/s setting controls the maximum rate
at which the engine speed can be changed. These
affect automatic and manual speed control and any
other speed control features.
RPM Setting >
Max Speed
500 ~ 4000 RPM
in 1 RPM increments
RPM Setting >
Speed Bias
0 ~ 600 RPM
in 1 RPM increments
RPM Setting >
TSC1 RPM/s
Disable
10 ~ 300 RPM/s
in 10 RPM/s increments
* Note that the minimum ramp rate is 1.25 RPM/s. If the speeds to ramp between and the ramp delay give a
RPM/s below this value, then 1.25 RPM/s will be used. For example, a speed difference of 300 RPM and a ramp
time of 300 s gives 1 RPM/s, but 1.25 RPM/s will be used instead, giving a ramp time of 240 s (300 RPM ÷ 1.25
RPM/s = 240 s).
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...