DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
34
9M02-9249-A001-EN
Revision A
Methods
Description
Switched inputs Momentary Start and Momentary Stop can be used for starting
and stopping of the engine. Unlike other inputs, they only have to be activated for
a short period of time.
When the battery voltage drops below a certain level, the engine will start and run
for a predetermined amount of time.
When the scheduled exerciser interval occurs, the engine will start and run for a
predetermined amount of time.
When a scheduled event occurs, the engine will start and run for the programmed
amount of time.
When a properly configured Auxiliary sensor falls below / rises above a certain
point, the engine will start as determined by the Auxiliary Sensors > Mode Select
settings.
When a certain command is sent to the controller over Modbus, the engine will
start. See the TOUGH Series Modbus Reference Manual for more information.
J1939 Start
Start/stop command sent over the J1939 CANbus; for example, from the TR100
or a remote telemetry device. The controller will display either
“J1939 Run” or
“J1939 Remote” as the reason for starting.
Float AutoStart
Start triggered by the Float 1 or Float 2 switched inputs.
ECM Power On
This is not a starting mode like the others. In Auto Mode, if the AUTO button is
held for 3 seconds, the fuel output is turned on for 1 hour.
“ECM Power On” will
be displayed on the screen.
Pressing and holding the AUTO button again within the hour will refresh for
another hour. This feature can be used to turn on or activate equipment powered
by the fuel output. Often this is used by a tech to power the ECM on an electronic
engine so that a diagnostic tool can obtain information from the ECM.
WARNING
SEE THE
SECTION FOR MORE INFORMATION ON HOW IT
AFFECTS STARTING AND STOPPING.
AVERTISSEMENT
VOIR LA SECTION
USING COOLDOWN MODE USING COOLDOWN MODE
D'INFORMATIONS SUR LA FAÇON DONT CELA PEUT AFFECTER LE DÉMARRAGE ET
L'ARRÊT.
4.1.1 Starting / Cranking Behavior
Crank disconnect is only monitored at the beginning of cranking. If the engine is already running, the starter
motor (output set to Crank) may turn on briefly.
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...