5.8.2 Modbus (RS485)
The Modbus functionality on the controller provides interface ability to PLCs, SCADA and building management
systems. For detailed information about the Modbus registers and their interpretations, please refer to the
TOUGH Series Modbus Reference Manual, which can be found at
It uses the Modbus RTU communication protocol and is configured as a slave only.
Name
Range / Values
Default
Description
Device Address
1 ~ 247
in 1 increments
1
The device address of the controller.
Baud Rate (BPS)
9600, 19200,
38400, 57400
9600
The speed at which the controller (slave)
communicates with the master.
5.9
Other Config
This section contains miscellaneous settings.
5.9.1 Password
A password is required to change certain settings. The Password menu is used to change this password and to
control if and when the user is prompted for a password.
Other Config > Passcode
Name
Range
Default
Description
Bypass
Disable or Enable
Disable
If enabled, a password is not required to change
settings.
Timeout
0 ~ 120 min
in 1 min increments
10 min
How long after the password is entered before the user
is required to enter it again.
The timeout is implemented as a simple countdown
timer. The following apply:
•
If the bypass time is changed, this new bypass time
will not be loaded until the countdown timer has
expired and the user enters the password.
•
The countdown timer is stored in non-volatile
memory and is “paused” when the controller is
powered off. The counter will resume when the
controller is powered on again.
•
Any button press in the menu will reset the timer.
Passcode
0000 ~ 9999
0000
The four numeric digits that make up the password.
5.9.2 Settings Name / ID
If you are storing settings from the RapidCore Configurator Software, a custom name can be entered to allow
users to determine the settings that are stored in the controller. This custom name, called
“Configuration Name”
(ID in the controller), is found under Options in the settings tab of the Configurator Software. There is no
controller menu to set this ID. It can be up to 12 characters long.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...