DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
91
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
False Check
(False Restart
Detect Time)
5 ~ 30 s
in 1 s intervals
8 s
Amount of time after successful cranking
to monitor for a false restart. A false
restart is defined as the speed dropping
below 250 RPM for 2 seconds. If this time
expires and the engines stalls out, the
controller will not attempt a restart.
This time starts from crank success.
Tip: It takes up to 2 seconds for the false restart to be triggered. In addition, it takes time for the engine speed to
drop below 250 RPM. These should be measured and added to the desired False Check setting.
For example, when the speed is disconnected, it takes approximately 2.5 s for the speed sensing to record
0 RPM when the speed sensing is set to a magnetic input at a speed of 3200 Hz/1800 RPM. This totals 4.5 s
when you include the 2 s for the false restart delay. So, if the desired monitoring period is 10 s, the False Check
setting should be set to 15 s.
5.6.1.3
OFF Button Function
The OFF button on the front panel of the controller can be configured to function in three different ways while the
engine is running. The following table describes each of these functions.
Function
Description
Cooldown
This function causes the controller to go into cooldown. Pressing the OFF button again
will cause the engine to shut down.
Shutdown
This function bypasses cooldown and causes the engine to shut down.
Force Cooldown
This function causes the controller to activate the cooldown process. Pressing the OFF
button will have no effect as the controller is forcing the engine to perform a full cool
down.
WARNING
IF THE CONTROLLER RECEIVES A COMMAND TO START FROM THE REMOTE START OR
FRONT PANEL RUN BUTTON WHILE IN COOLDOWN, IT WILL LEAVE THE COOLDOWN MODE
AND GO BACK TO RUNNING MODE.
AVERTISSEMENT
SI LE CONTROLEUR REÇOIT UNE COMMANDE DE DEMARRAGE A PARTIR DE LA COMMANDE
DE DEMARRAGE A DISTANCE, OU DU BOUTON RUN (MARCHE) DU PANNEAU DE COMMANDE
ALORS QU'IL EST EN MODE COOLDOWN (REFROIDISSEMENT), IL QUITTERA LE MODE
COOLDOWN (REFROIDISSEMENT) ET REVIENDRA AU MODE RUNNING (MARCHE).
5.6.1.4
Idle
The controller ignores under speed, voltage and frequency warnings and failures when active. If using J1939, the
controller will broadcast TSC1 as the Idle Speed parameter found in the
section.
!
!
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...