2.6
Wiring Considerations
The following sections are meant to describe certain wiring configurations and are for illustrative purposes only.
Not all applications are the same. Please ensure that you modify these examples to fit your unique system
requirements.
2.6.1 Remote Start Contact (Start/Stop)
As of firmware version 1.60, the Start/Stop is factory defaulted to switch input B (changeable) and the trigger is
factory defaulted to Close +BAT. For older firmware versions, you must set Start/Stop to Switched Input B or as
desired and set the trigger mode to Close +BAT. The trigger can be set to any of four options but Close +BAT
gives the best immunity to noise.
For runs over 20 ft (6.1 m), especially in noisy environments, Cattron recommends connecting the Start/Stop to
an external relay. The relay needs to be located as close to the controller as possible.
2.6.2 Emergency Stop Wiring
If Emergency Stop functionality is required, it must be an external mushroom-style switch wired in series with the
fuel or ignition supply to ensure reliable and immediate shutdown upon activation.
The following figure shows is an example wiring diagram of a double pole, single throw switch being used to
activate the e-stop input and cut power to the fuel solenoid. In this configuration, the e-stop is activated when
there is an open circuit to the switched input, and it is inactive when the input detects battery positive voltage.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...