DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
62
9M02-9249-A001-EN
Revision A
Name
Active Mode
Description
RPM Increment
Running
Output is used to trigger inputs on an ECM to control
speed. See
section for more
information.
RPM Decrement
Running
Output is used to trigger inputs on an ECM to control
speed. See
section for more
information.
DEF Fluid Pump
Running
Active when DEF Fluid Level falls below the DEF Low
Level and stays active until the level rises above the DEF
High Level. See
section for more
information.
Genset Disable
Global
Disables the generator during a stationary Regen on
Kubota engines (see Aftertreatment in the J1939
Reference Manual) or also during an engine idle condition
from the idle switched input. Automatic idle is ignored. If the
generator voltage is not below the under voltage setpoint in
10 seconds, the controller will shut down the engine on
“Generator Disable Failure.”
Dummy Load
Running
Output is controlled by the
feature.
Breaker Trip
Running
Output is controlled by the
features. The Breaker Trip only reacts to over
current faults; it does not activate for other failures.
Auto Idle
Warm-up, Cooldown
Active at the start of delay to start until the end of warm-up
if warmup idle is enabled. Also active during cooldown if
cooldown idle is enabled. See Warm-up Idle and Cooldown
Idle in
. This output does not react to the Idle
switched input.
Warning Functions
Functions
Low Engine
Temperature
High Engine
Temperature
Low Oil Pressure
Under Speed
Over Speed
Low Fuel Level
High Fuel Level
Low Battery Voltage
High Battery Voltage
Under Frequency
Over Frequency
AC Under Voltage
AC Over Voltage
Over Current
Fuel In Basin
Battery Charger Fault
Configurable Warning 1 Configurable Warning 2 Auxiliary Sensor 1
Auxiliary Sensor 2
Auxiliary Sensor 3
Auxiliary Sensor 4
Name
Active Mode
Description
Load Imbalance
Running
AC current phases do not match. (
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...