Exerciser Sequence
If the controller is in the Off Mode, if the emergency stop is activated, or if the start inhibit is active, then the
exerciser will not run. The event
“Bypass Exerciser” will be logged in the Events History and the exerciser will run
again at the next scheduled time as determined by the
“Repeat Days” setting.
5.6.2.2
Week Scheduler
The weekly scheduler allows up to 16 unique weekly exercise times to be created. By default, all schedulers are
disabled.
Timers > Week Scheduler
Name
Range
Description
Weekday
Sunday ~ Saturday
The day of the week on which the exercise will take place.
Start time
24-hour clock
in 1 min increments
The time at which the exercise should start on the given day. At
the selected time, a one-minute pre-alarm is displayed on the
LCD screen. The controller starts after this one-minute period.
Run time
10 ~ 1440 min
in 1 min increments
The duration of the exercise run period. Up to one day.