xGenConnect Installation and Programming Guide
25
If a device is placed in a plastic housing the earth lug of the device does not have
to be connected.
In one building several cabinets or devices are earthed to a safety ground. The
safety ground for the building must be checked by a licensed contractor.
Shielding
The shielding of all shielded cables used in the system should only be connected
at one side to one common earthing point in a building. If a shielded LAN cable is
routed via more than one plastic device the shielding from incoming and outgoing
cable must be connected.
Termination Links
Put a jumper across TERM on the panel and the furthest device to ensure correct
RS-485 termination and avoid communication issues with signal reflection, etc.
Installing NXG-8 panel / NX-003 housing
1. The xGenConnect should be located away from
damp areas (e.g. bathrooms, kitchens), away from
sources of heat, dust or interference (e.g. air
conditioners, washing machines, dryers,
refrigerators) and away from external walls.
Due to safety reasons it is not allowed to wall-
mount the device higher that 2 meters from the
floor.
2. The metal enclosure should be installed with the
door opening from the top to bottom.
3. Guides are cut into the enclosure to hold the
panel, two on the top and two on the bottom. Two
plastic brackets are pre-installed on the
xGenConnect. Slide the panel into the guides as
shown in the diagram. The terminal strip should
face towards you once installed.
4. A plastic strap is provided to allow the door to
form a temporary surface to hold light parts.
5. When installing permanent, fixed wiring, insert an
easily accessible, dedicated all-pole circuit
breaker in the power distribution network.
Summary of Contents for xGenConnect
Page 1: ...xGenConnect Installation and Programming Guide P N 466 5545 EN REV J ISS 26OCT22...
Page 4: ......
Page 12: ...viii xGenConnect Installation and Programming Guide...
Page 93: ...xGenConnect Installation and Programming Guide 81 Web Page...
Page 109: ...xGenConnect Installation and Programming Guide 97 Instructions 1 Go to Zone Type...
Page 117: ...xGenConnect Installation and Programming Guide 105 Webpage...
Page 156: ...144 xGenConnect Installation and Programming Guide...
Page 166: ...154 xGenConnect Installation and Programming Guide...