KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
263
0.5°C
1.0°C
This parameter is used to specify the step size for manual setpoint adjustment.
10.24.99 Setpoint adjustment - Setpoint adjustment master/slave via communication object
Options:
1-byte counter value
Relative temperature value
Absolute temperature value
This parameter is used to specify whether the setpoint adjustment for master/slave is carried
out via a temperature value or a 1-byte counter value.
10.24.100
Setpoint adjustment — Resetting of the manual adjustment for receipt of a basic
setpoint
Options:
Deactivated
Activated
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.